3SK1122-2AB40
SIRIUS SAFETY RELAY ADV ELECT. 3+1

From SIEMENS

SIRIUS safety relay Basic unit Advanced series 3 electronic enabling circuits 1 electronic signaling circuit Us = 24 V DC Spring-type terminal (push-in)
General technical data
Product brand nameSIRIUS
Product categorySafety relays
Product designationsafety relays
Design of the productSolid-state enabling circuits
Protection class IP of the enclosureIP20
Protection against electrical shockfinger-safe
Insulation voltage rated value50 V
Ambient temperature
during storage-40 ... +80 °C
during operation-25 ... +60 °C
Air pressure acc. to SN 3120590 kPa ... 106 kPa
Relative humidity during operation10 ... 95 %
Installation altitude at height above sea level maximum2 000 m
Vibration resistance acc. to IEC 60068-2-65 ... 500 Hz: 0.75 mm
Shock resistance10g / 11 ms
Surge voltage resistance rated value800 V
EMC emitted interferenceIEC 60947-5-1, Class A
Installation environment regarding EMCThis product is suitable for Class A environments only. It can cause undesired radio-frequency interference in residential environments. If this is the case, the user must take appropriate measures.
Overvoltage category3
Degree of pollution3
Number of sensor inputs 1-channel or 2-channel1
Design of the cascadingyes
Type of the safety-related wiring of the inputssingle-channel and two-channel
Product feature cross-circuit-proofYes
Safety Integrity Level (SIL)
acc. to IEC 615083
Performance level (PL)
acc. to EN ISO 13849-1e
Category acc. to EN ISO 13849-14
Safe failure fraction (SFF)99 %
PFHD with high demand rate acc. to EN 620610.0000000013 1/h
PFDavg with low demand rate acc. to IEC 615080.000007
T1 value for proof test interval or service life acc. to IEC 6150820 y
Hardware fault tolerance acc. to IEC 615081
Safety device type acc. to IEC 61508-2Type B
Number of outputs as contact-affected switching element
as NC contact
— for signaling function instantaneous contact0
— for signaling function delayed switching0
— safety-related instantaneous contact0
— safety-related delayed switching0
as NO contact
— for signaling function instantaneous contact0
— for signaling function delayed switching0
— safety-related instantaneous contact0
— safety-related delayed switching0
Number of outputs as contact-less semiconductor switching element
safety-related
— delayed switching0
— instantaneous contact3
for signaling function instantaneous contact1
Stop category acc. to DIN EN 60204-10
General technical data
Design of input
cascading input/functional switchingYes
feedback inputYes
Start inputYes
Type of electrical connection Plug-in socketNo
Operating frequency maximum2 000 1/h
Switching capacity current
of semiconductor outputs at DC-13 at 24 V2 A
Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs requirednot required
Wire length
with Cu 1.5 mm² and 150 nF/km per sensor circuit maximum4 000 m
Make time with automatic start
at DC maximum85 ms
Make time with automatic start after power failure
typical6 500 ms
maximum6 500 ms
Make time with monitored start
maximum85 ms
Backslide delay time after opening of the safety circuits typical40 ms
Backslide delay time in the event of power failure
typical0 ms
maximum0 ms
Recovery time after opening of the safety circuits typical30 ms
Recovery time after power failure typical6.5 s
Pulse duration
of the sensor input minimum60 ms
of the ON pushbutton input minimum0.15 s
Control circuit/ Control
Type of voltage of the control supply voltageDC
Control supply voltage
at DC
— rated value24 V
Operating range factor control supply voltage rated value of magnet coil
at DC0.8 ... 1.2
Power loss [W] typical2 W
Installation/ mounting/ dimensions
Mounting positionany
Required spacing for grounded parts at the side5 mm
Required spacing with side-by-side mounting at the side0 mm
Mounting typescrew and snap-on mounting
Width22.5 mm
Height100 mm
Depth121.6 mm
Connections/Terminals
Type of electrical connectionPush-in terminal
Type of connectable conductor cross-sections
solid1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
finely stranded
— with core end processing1x (0.5 ... 1.0 mm²), 2x (0.5 ... 1.0 mm²)
— without core end processing1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
Type of connectable conductor cross-sections at AWG conductors
solid1x (20 ... 16), 2x (20 ... 16)
stranded1x (20 ... 16), 2x (20 ... 16)
Product Function
Product function parameterizableSensor floating / sensor non-floating, monitored start / autostart, 1-channel / 2-channel sensor connection, cross-circuit detection, startup testing, antivalent sensors, 2-hand switches
Suitability for operation Device connector 3ZY12Yes
Suitability for interaction press controlYes
Suitability for use
safety switchYes
Monitoring of floating sensorsYes
Monitoring of non-floating sensorsYes
magnetically operated switch monitoringYes
safety-related circuitsYes

External links