| WITHDRAW. NON-AUT. CIRCUIT-B. 4-POLE, SIZE I IN=1600A TO 500V, AC50/60HZ ICU=66KA AT 500V ONLY MOD-CENTER |
Model |
product brandname | SENTRON |
Product designation | 3WT air circuit breaker |
Design of the product | IEC 60947-2 |
Type of the driving mechanism | Manual operating mechanism with stored energy feature, with mechanical closing |
Type of the driving mechanism / motor drive | No |
Design of the overcurrent release | Without, version old |
General technical data |
Number of poles | 4 |
Field of application | NON-AUTOMATIC CIRCUIT-BREAKER |
Size of the circuit-breaker | I |
Electrical endurance (switching cycles) / typical | 10 000 |
Usage category | A |
circuit-breaker / Design | 3WT8 |
Mechanical service life (switching cycles) / typical | 16 000 |
Equipment marking / acc. to DIN 40719 extended according to IEC 204-2 / acc. to IEC 750 | Q |
Voltage |
Rated operational voltage Ue / max. | 500 V |
Rated insulation voltage Ui | 1 000 V |
Insulation voltage / at AC / rated value | 1 000 V |
Surge voltage resistance / rated value | 12 kV |
Protection class |
Protection class IP | IP20 |
Dissipation |
Power loss [W] | |
maximum | 140 W |
Electricity |
rated current In | |
max. | 1 600 A |
at 40 Cel | 1 600 A |
at 50 Cel | 1 600 A |
Continuous current / rated value | 1 600 A |
Derating temperature / for the rated value of the continuous current | 50 °C |
Short-time current resistance (Icw) | |
limited to 0.5 s / rated value | 50 kA |
limited to 1 s / rated value | 50 kA |
limited to 2 s / rated value | 30 kA |
limited to 3 s / rated value | 25 kA |
Main circuit |
Operating frequency / 1 / rated value | 50 Hz |
Operating voltage | |
for main current circuit / at AC / at 50 Hz / maximum | 500 V |
for main current circuit / at AC / at 60 Hz / maximum | 500 V |
Operating current | |
at 40 °C / rated value | 1 600 A |
at 50 °C / rated value | 1 600 A |
at 60 °C / rated value | 1 500 A |
at 70 °C / rated value | 1 350 A |
Auxiliary circuit |
Operating current / of auxiliary contacts / at AC-15 / at 230 V | 6 A |
Suitability |
Suitability for use | |
Disconnecting means | Yes |
Product details |
Product component | |
Trip indicator | No |
Auxiliary switch | Yes |
Voltage trigger | No |
undervoltage release | No |
Product extension / optional / motor drive | Yes |
Product function |
Product function | |
Overload protection | No |
Accessories |
accessories | No further Z accessories |
Short circuit |
Operational short-circuit current breaking capacity (Ics) | |
at 240 V / rated value | 66 kA |
at 415 V / rated value | 66 kA |
at 500 V / rated value | 66 kA |
Maximum short-circuit current breaking capacity (Icu) | |
at 240 V / rated value | 66 kA |
at 400 V / rated value | 66 kA |
at 415 V / rated value | 66 kA |
at 440 V / rated value | 66 kA |
at 480 V / rated value | 66 kA |
at 500 V / rated value | 66 kA |
Connections |
Arrangement of electrical connectors / for main current circuit | Laminated contacts in guide frame |
Type of connection, main circuit | LAMINATED CONTACT IN GUIDE FRAME |
Type of electrical connection / for main current circuit | busbar connection |
Mechanical Design |
Type of mounting | WITHDRAWABLE UNIT |
Mounting position | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
Mounting type | drawer unit |
Environmental conditions |
Ambient temperature | |
during operation / minimum | -20 °C |
during operation / maximum | 70 °C |
during storage / minimum | -40 °C |
during storage / maximum | 80 °C |